aSENSE™
aSENSE is an advanced transmitter for installation in the climate zone. It measures both CO2 concentration and temperature. The data is transmitted to a BMS system or controller and can be configured with UIP Software. Detected values are transformed into two analogue output signals that can be transmitted to a system master or DDC. aSENSE is available both with and without LCD display for FIXED installation in the climate zone as well as in the ventilation duct.
Key benefits
-Maintenance-free in normal applications.
-Contributes to lower energy costs when it is applied in a Demand Control Ventilation (DCV) strategy.
-Internal automatic self diagnostics.
-2 analogue outputs as standard (V/mA). Relay output as option.
-Cost-efficient RS485 communication as option.
-Internal 2-channel logger as option.
Applications
aSENSE is designed to control ventilation by transmitting the measured carbon dioxide and temperature value to the system´s Master or DDC. The transmitter is flexible and suits many different ventilation strategies. According to most building regulations, the fresh air flow should, in rooms where people stay more than occasionally, be at least 7 litres/sec and person.
If the room occupants are adults with a light work-load and the outdoor CO2 concentration is 350 ppm, this airflow answers directly to an in-door CO2 concentration of 1040 ppm.
According to National Boards of Occupational Safety and Health, the CO2 concentration can therefore be used as an indicator of the Indoor Air Quality (IAQ). A CO2 concentration below 1000 ppm should then always be the aim.
Specifications
| Standard Specification | |
| Operating Principle | Non-dispersive infrared (NDIR) |
| Measured gas | CO2 |
| Measurement range CO2 | 0 - 2 000 ppm |
| Accuracy | ±30 ppm ±3% of reading |
| Dimensions | 120 mm x 82 mm x 30 mm |
| Maintenance | Maintenance-free* |
| Life Expectancy | > 15 years |
| Operation temperature range | 0 to +50 °C |
| Operation humidity range | 0 to 95% RH (non-condensing) |
| Power supply | 24 VAC/VDC±20%, 50-60 Hz (half-wave rectifier input) |
| Power Consumtion | < 3 Watts average |
| Response timeT90 | 2 min. diffusion time |
| Warm-up time | ≤ 1 min. (@ full specs ≤ 10 minutes) |
| Communication | Uart ( Modbus) |
| Outputs | |
| OUT 1 linear output | 0/2 to 10 V DC or 0/4-20mA (CO2) |
| OUT 2 linear output | 0/2 to 10 V DC or 0/4-20mA (°C) |
*Maintenance-free with using SenseAir ABC logic Self calibration using for normal indoor applications.
Art.no.
| Art.no. | Product | Additional features |
| 040-8-0001 | aSENSE | |
| 040-8-0002 | aSENSE - Disp | Display |
| 040-8-0003 | aSENSE - RL | No display, relay |
| 040-8-0025 | aSENSE- Disp RL | Display, relay |
| 040-8-0028 | aSENSE Ind- Disp RL | Display, relay, protection class IP54 |
| 040-3-0005 | aSENSE Ind -10% Disp RL MB | Display, relay, 0 to 10%vol (CO2), Modbus prepared |
| 040-8-0029 | aSENSE - MB RS485 | No display, Modbus RS485 communication |
| 040-8-0096 | aSENSE - Disp Lon | Display, LON communication |
| 040-8-0091 | aSENSE - Disp MB RS485 LOG | Display, Modbus RS485 communication, Logger |